AXIAL DIRECT DRIVE SMOKE FAN WITH CAST ALUMINUM IMPELLER IN SOUNDPROOF CABINET - 400ºC/2H
MANUFACTURING FEATURES
• BOX: Manufactured in galvanised steel sheet with thermalproofing. Soundproofing cabinetswith thermo-acoustic insulation, Bs1d0 fire class. Removable panels for easy motor access and fan maintenance.
• INSIDE FAN: For sizes from 45 to 80 we use model WMA Fire F400. For larger sizes from 90 to 125 we use model SCA FIRE F400.
• Modular motor-impeller assembly.
• Cast aluminum impeller with variable pitch angle.
• Polyester powder finishing coat.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation certified 400ºC/2H. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
APPLICATIONS
Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Cabinet design simplifies installation in rectangular duct systems.
• Maximum working temperature: 60ºC.
UNDER REQUEST
• Supply 100% reversible impeller.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2272