fan image
Model
JF FIRE 400 T2/T4 UN

JF FIRE 400 T2/T4 UN

LOW PROFILE AXIAL JET FAN - 400ºC/2h

MANUFACTURING FEATURES:

The JF models are composed of an axial fan and two silencers.
FAN:
• Axial fan with galvanized steel casing. The connection box is accessible by the side from a removable door.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation, certified 400ºc/2h. Standard voltages 230/400V 50Hz for 1 speed motors and 400V 50Hz for 2 speed motors.
SILENCERS:
• Casing in galvanized steel. Inner duct made of perforated galvanized steel sheet. The silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.
• Unidirectional JF FIRE F400 UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.
• Reversible JF FIRE F400 RE is equipped with protection guards on both sides.

 

APPLICATIONS:
• Conceived for car parkings and large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively. An optimized design minimizes the height needed for their installation and assures a silent operation.
• Maximum working temperature: 60ºC.

 


Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2273

Fan

Max flow
8060 m³/h
Weight
70 Kg

Motor

Power
1,1/0,18 kW
RPM Motor
2850/1450
I max. 400 V
2,36/0,59
Size
80
Weight
11.2 Kg
Efficiency
76/70 %
FP
0.84/0.76
JF FIRE 400 T2/T4 UN
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

JF FIRE 400 T2/T4 UN

Dimensions scheme
A B C D E F G H I J L M ØK Thrust (N)
2415 758 440,5 1025 720 664 434 506 233 20 122 365 15 48/12

JF FIRE 400 T2/T4 UN

Electrical scheme

JF FIRE 400 T2/T4 UN

Model
INT 400 25A 6P
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
INT 25 6P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)