JF FIRE 400 T2 UN

JF FIRE 400 T2 UN

LOW PROFILE AXIAL JET FAN - 400ºC/2h

MANUFACTURING FEATURES:

The JF models are composed of an axial fan and two silencers.
FAN:
• Axial fan with galvanized steel casing. The connection box is accessible by the side from a removable door.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation, certified 400ºc/2h. Standard voltages 230/400V 50Hz for 1 speed motors and 400V 50Hz for 2 speed motors.
SILENCERS:
• Casing in galvanized steel. Inner duct made of perforated galvanized steel sheet. The silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.
• Unidirectional JF FIRE F400 UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.
• Reversible JF FIRE F400 RE is equipped with protection guards on both sides.

 

APPLICATIONS:
• Conceived for car parkings and large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively. An optimized design minimizes the height needed for their installation and assures a silent operation.
• Maximum working temperature: 60ºC.

 


Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2273

Fan

Max flow
8060 m³/h
Weight
70 Kg

Motor

Power
1,1 kW
RPM Motor
2860
I max. 400 V
2,39
Size
80
Weight
14 Kg
Efficiency
80.5 %
FP
0.85
JF FIRE 400 T2 UN
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

JF FIRE 400 T2 UN

Dimensions scheme
A B C D E F G H I J L M ØK Thrust (N)
2415 758 440,5 1025 720 664 434 506 233 20 122 365 15 48

JF FIRE 400 T2 UN

Electrical scheme

JF FIRE 400 T2 UN

Model
INT 25 3P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT 400 25A 3P
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
SFC 230 I 4,2A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
SFC 400 III 3,6A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current