CENTRIFUGAL DIRECT DRIVE FAN WITH BACKWARD CURVED IMPELLER IN CASING
MANUFACTURING FEATURES
• Casing:
- Made of galvanised steel sheet with upstream and downstream connecting flanges and access doors.
• Motor support:
- Galvanised steel plate, motor with flanges fixed on 2 poles. Removable plate/support/impeller set.
• Impeller:
- Backward impeller with self-cleaning system, in galvanised steel, dynamically balanced.
- Direct drive on the motor shaft.
• Motor:
- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander
APPLICATIONS
• Ventilation in technical, industrial or commercial facilities.
A | B | C | D | E | H | I | K | L | L1 | L2 |
---|---|---|---|---|---|---|---|---|---|---|
700 | 700 | 700 | 1043,5 | 343,5 | 278 | 211 | 26 | 595,7 | 264,9 | 329,3 |
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.
MANUFACTURING FEATURES
• Connection flange for rectangular outlet of BCU, to make the connection to a circular duct easier.
• Made of galvanized steel.
MANUFACTURING FEATURES
• Support made of galvanized steel.
MANUFACTURING FEATURES
• Outdoor flange with bird guard for BCU.
• Made of galvanized Steel.
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
MANUFACTURING FEATURES
• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:
Arrow (mm.) r.p.m.
20 mm >600 r.p.m.
30 mm >500 r.p.m.
• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.
APPLICATION
• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.
Nº | Family | Name | Qty |
---|---|---|---|
1 | MOTOR | 0,75/0,12kW T4/T8 B3 400V | x1 |
2 | TURBINE | THRE R63B1 400X140x19 RD | x1 |
3 | INLET CONE | ED11 400 | x1 |