RK BOX PLUS
Model
RK BOX PLUS

RK BOX PLUS

VENTILATION BOX WITH BACKWARD IMPELLER

MANUFACTURING FEATURES:

  • Ventilation box with 30 mm aluminum profile structure, nylon corners, galvanized sandwich panels with internal insulation rockwool (25mm thickness) class A1 (non-combustible) of 90kg/m3 density. All panels are equipped with "fastening system" for the quick assembly and disassembly whenever required, either for cleaning, maintenance or exchanging of panels.
    • Centrifugal fan with motor coupled directly to the impeller, plugfan type.
    • Circular inlet to facilitate duct connection. Open outlet.
    • Models with AC motor inside the air flow. Standard asynchronous squirrel cage motor with IP-55 protection and Class F insulation. Standard voltages of 230V50Hz for single phase motors, 230/400V50Hz & 400/690V 50Hz for three-phase 1 speed motors and 400V50Hz for 2 speed motors.
  • Backward curved single inlet impeller of high performance with self-cleaning system made of steel. Balanced statically and dynamically at origin.
    • Exchangeable panels.

 

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum working temperature: three phase 60ºC.

Fan

Max flow
13685 m³/h
Weight
122 Kg

Motor

Power
3 kW
RPM Motor
1420
I max. 230 V
10,7
I max. 400 V
6,17
Size
100L
Weight
34 Kg
Efficiency
87.7 %
FP
0.82
RK BOX PLUS
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

RK BOX PLUS

Dimensions scheme
A B C D E F G H I
1030 1030 1097 628 1030 47 720 970 1142

RK BOX PLUS

Electrical scheme

RK BOX PLUS

Model
INT 25 3P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
SFC 400 III 8A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

RK BOX PLUS

Spare parts scheme
Family Name Qty
1 MOTOR 3KW T4 B5 230/400V x1