BDS FIRE F400
Model
BDS FIRE 500

BDS FIRE 500

CENTRIFUGAL BELT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN SOUNDPROOF CABINET - 400ºC/2h

MANUFACTURING FEATURES:

• MPBI range fans assembled in soundproof cabinets with insulated panels.
• Fan assembled on antivibration mountings.
• Simple inlet backward impeller with self-cleaning system.
• Supplied with motor, pulleys and belts.
• Interchangeable panels to allow different fan positions.
• Gland connection included.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.

APPLICATIONS:

Designed for inline installation, indoor or outdoor assembly, they are suitable for:
• Smoke emergency exhaust with motor outside the hazardous area.
• Industrial and professional kitchen hoods.
• Maximum working temperature: carried air: 130ºC, ambient: 60ºC.

UNDER REQUEST:

• 2 speed motors.
• Orentation:
- LG90 (horizontal).
- LG0 (vertical outlet).
• Sandwich insulation.
• 60Hz fans and special voltages.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2276

Fan

Max flow
14300 m³/h
BDS FIRE 500
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

BDS FIRE 500

Dimensions scheme
A B C D E F G H I J K L M N O ØR P Q S T U V W
1423 1100 732 1315,7 997 627 1249,5 928,5 561 1259,5 881 1319,5 930 104 355 498 40,5 60 399 643,7 60 639 341

BDS FIRE 500

Electrical scheme

BDS FIRE 500

Model
BA-400 50
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
INT (GENERIC)
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT F400 (GENERIC)
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
AVS (GENERIC)
Information
ANTI-VIBRATION SPRING BLOCK

MANUFACTURING FEATURES

• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:

Arrow (mm.)          r.p.m.
    20 mm          >600 r.p.m.
    30 mm          >500 r.p.m.

• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.

APPLICATION

• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.