BDS FIRE F400
Model
BDS FIRE 450

BDS FIRE 450

CENTRIFUGAL BELT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN SOUNDPROOF CABINET - 400ºC/2h

MANUFACTURING FEATURES:

• MPBI range fans assembled in soundproof cabinets with insulated panels.
• Fan assembled on antivibration mountings.
• Simple inlet backward impeller with self-cleaning system.
• Supplied with motor, pulleys and belts.
• Interchangeable panels to allow different fan positions.
• Gland connection included.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.

APPLICATIONS:

Designed for inline installation, indoor or outdoor assembly, they are suitable for:
• Smoke emergency exhaust with motor outside the hazardous area.
• Industrial and professional kitchen hoods.
• Maximum working temperature: carried air: 130ºC, ambient: 60ºC.

UNDER REQUEST:

• 2 speed motors.
• Orentation:
- LG90 (horizontal).
- LG0 (vertical outlet).
• Sandwich insulation.
• 60Hz fans and special voltages.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2276

Fan

Max flow
12990 m³/h
BDS FIRE 450
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

BDS FIRE 450

Dimensions scheme
A B C D E F G H I J K L M N O ØR P Q S T U V W
1323 1003 692 1215,7 900 587 1149,5 831,5 521 1159,5 841 1219,5 890 100 328 448 40,5 60 375 587,7 60 573 310

BDS FIRE 450

Electrical scheme

BDS FIRE 450

Model
BA-400 45
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
INT (GENERIC)
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT F400 (GENERIC)
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
AVS (GENERIC)
Information
ANTI-VIBRATION SPRING BLOCK

MANUFACTURING FEATURES

• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:

Arrow (mm.)          r.p.m.
    20 mm          >600 r.p.m.
    30 mm          >500 r.p.m.

• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.

APPLICATION

• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.