fan image
Model
BOX CA FIRE 56 T4 (A2:6) F300

BOX CA FIRE 56 T4 (A2:6) F300

AXIAL SMOKE FAN WITH CAST ALUMINUM IMPELLER DIRECT DRIVE IN SOUNDPROOF CABINET - 300ºC/1H

MANUFACTURING FEATURES

• BOX: Manufactured in galvanised steel sheet with thermalproofing. Soundproofing cabinets with thermo-acoustic insulation, Bs1d0 fire class. Removable panels for easy motor access and fan maintenance.
• INSIDE FAN: For sizes from 45 to 80 we use model WMA FIRE F300. For larger sizes from 90 to 125 we use model SCA FIRE F300.
• Modular motor-impeller assembly.
• Cast aluminum impeller with variable pitch angle.
• Polyester powder finishing coat.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation certified 300ºC/1H. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.



APPLICATIONS

Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Cabinet design simplifies installation in rectangular duct systems.
• Maximum working temperature: 60ºC.


UNDER REQUEST

• Supply 100% reversible impeller.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2405

Fan

Max flow
13100 m³/h
BOX CA FIRE 56 T4 (A2:6) F300
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

BOX CA FIRE 56 T4 (A2:6) F300

Dimensions scheme
A B C D E F G H J K L M N O
781.5 781.5 542 630 76 630 76 30 665 610 11 715 35 60

BOX CA FIRE 56 T4 (A2:6) F300

Electrical scheme

BOX CA FIRE 56 T4 (A2:6) F300

Model
SFC (GENERIC)
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
INT (GENERIC)
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT F400 (GENERIC)
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
AVS (GENERIC)
Information
ANTI-VIBRATION SPRING BLOCK

MANUFACTURING FEATURES

• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:

Arrow (mm.)          r.p.m.
    20 mm          >600 r.p.m.
    30 mm          >500 r.p.m.

• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.

APPLICATION

• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.