BCU FIRE 355 T2 2,2KW F400

BCU FIRE F400
Model
BCU FIRE 355 T2 2,2KW F400

CENTRIFUGAL DIRECT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN CASING - 400ºC/2h

MANUFACTURING FEATURES

• Casing:
- Made of galvanised steel sheet with upstream and downstream connecting flanges and access doors.
• Motor support:
- Galvanised steel plate, motor with flanges fixed on 2 poles. Removable plate/support/impeller set.
• Impeller:
- Backward impeller with self-cleaning systeml, in galvanised steel, dynamically balanced.
- Direct drive on the motor shaft.
• Motor:
- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander

APPLICATIONS

• Smoke extraction in high buildings and establishments with people.
• Ventilation and smoke exhaust in covered parkings.
• Ventilation in technical, industrial or commercial facilities.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2728

Fan

Max flow
6830 m³/h
Weight
73 Kg

Motor

Power
2,2 kW
RPM Motor
2840
I max. 230 V
7,97
I max. 400 V
4,58
Size
90L
Weight
25 Kg
Efficiency
85.9 %
FP
0.83

ERP

Fan sheet
Fan type
Unit for non-residential ventilation (LOT 6)
Tipology
Unidirectional
Other
None
Type of driver None
Values Requirements 2018
Max. efficiency (%)
56.61 46.75
Eff. heat recovery (%)
-
Absorbed power (kW) 2.152
Flow (m³/h)
4151.88
Static pressure (Pa)
996.77
Speed (m/s)
10.75
SFP
1865.66