BCU FIRE 315 T2 1,1KW F400

BCU FIRE F400
Model
BCU FIRE 315 T2 1,1KW F400

CENTRIFUGAL DIRECT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN CASING - 400ºC/2h

MANUFACTURING FEATURES

• Casing:
- Made of galvanised steel sheet with upstream and downstream connecting flanges and access doors.
• Motor support:
- Galvanised steel plate, motor with flanges fixed on 2 poles. Removable plate/support/impeller set.
• Impeller:
- Backward impeller with self-cleaning systeml, in galvanised steel, dynamically balanced.
- Direct drive on the motor shaft.
• Motor:
- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander

APPLICATIONS

• Smoke extraction in high buildings and establishments with people.
• Ventilation and smoke exhaust in covered parkings.
• Ventilation in technical, industrial or commercial facilities.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2728

Fan

Max flow
4410 m³/h
Weight
64 Kg

Motor

Power
1,1 kW
RPM Motor
2800
I max. 230 V
4,05
I max. 400 V
2,33
Size
80
Weight
16 Kg
Efficiency
82.7 %
FP
0.85

ERP

Fan sheet
Fan type
Unit for non-residential ventilation (LOT 6)
Tipology
Unidirectional
Other
None
Type of driver None
Values Requirements 2018
Max. efficiency (%)
54.02 42.62
Eff. heat recovery (%)
-
Absorbed power (kW) 1.105
Flow (m³/h)
2708.64
Static pressure (Pa)
756.62
Speed (m/s)
8.38
SFP
1468.55