CENTRIFUGAL DIRECT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN CASING - 400ºC/2h
MANUFACTURING FEATURES
• Casing:
- Made of galvanised steel sheet with upstream and downstream connecting flanges and access doors.
• Motor support:
- Galvanised steel plate, motor with flanges fixed on 2 poles. Removable plate/support/impeller set.
• Impeller:
- Backward impeller with self-cleaning systeml, in galvanised steel, dynamically balanced.
- Direct drive on the motor shaft.
• Motor:
- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander
APPLICATIONS
• Smoke extraction in high buildings and establishments with people.
• Ventilation and smoke exhaust in covered parkings.
• Ventilation in technical, industrial or commercial facilities.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2728
Fan sheet |
|||
---|---|---|---|
Fan type |
Unit for non-residential ventilation (LOT 6) |
||
Tipology |
Unidirectional | ||
Other |
None |
||
Type of driver | None | ||
Values | Requirements 2018 | ||
Max. efficiency (%) |
59.19 | 51.49 | |
Eff. heat recovery (%) |
- | ||
Absorbed power (kW) | 4.624 | ||
Flow (m³/h) |
11637.73 | ||
Static pressure (Pa) |
799.29 | ||
Speed (m/s) |
9.64 | ||
SFP |
1430.29 |