fan image
Model
BCU FIRE 500 T6 0,75KW F400

BCU FIRE 500 T6 0,75KW F400

CENTRIFUGAL DIRECT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN CASING - 400ºC/2h

MANUFACTURING FEATURES

• Casing:
- Made of galvanised steel sheet with upstream and downstream connecting flanges and access doors.
• Motor support:
- Galvanised steel plate, motor with flanges fixed on 2 poles. Removable plate/support/impeller set.
• Impeller:
- Backward impeller with self-cleaning systeml, in galvanised steel, dynamically balanced.
- Direct drive on the motor shaft.
• Motor:
- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander

APPLICATIONS

• Smoke extraction in high buildings and establishments with people.
• Ventilation and smoke exhaust in covered parkings.
• Ventilation in technical, industrial or commercial facilities.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2728

Fan

Max flow
6300 m³/h
Weight
146 Kg

Motor

Power
0,75 kW
RPM Motor
925
I max. 230 V
3,39
I max. 400 V
1,95
Size
90L
Weight
19 Kg
Efficiency
78.9 %
FP
0.73
BCU FIRE 500 T6 0,75KW F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

BCU FIRE 500 T6 0,75KW F400

Dimensions scheme
A B C D E H I K L L1 L2
900 900 900 1243,5 343,5 338 281 26 795,7 314,3 479,9

BCU FIRE 500 T6 0,75KW F400

Electrical scheme

BCU FIRE 500 T6 0,75KW F400

Model
INT 25 3P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT 400 25A 3P
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
EI DHUMAT 500
Information
OUTLET FLANGE FOR BCU

MANUFACTURING FEATURES

• Connection flange for rectangular outlet of BCU, to make the connection to a circular duct easier.
• Made of galvanized steel.

Model
DKF 500-560
Information
BCU FEET KIT

MANUFACTURING FEATURES

• Support made of galvanized steel.

Model
VIS DHUMAT 500-560
Information
OUTDOOR FLANGE WITH BIRD GUARD FOR BCU

MANUFACTURING FEATURES

• Outdoor flange with bird guard for BCU.
• Made of galvanized Steel.

Model
SFC 230 I 4,2A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
SFC 400 III 2,2A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

BCU FIRE 500 T6 0,75KW F400

Spare parts scheme
Family Name Qty
1 MOTOR 0,75kW T6 B3 230/400V x1
2 TURBINE THRE R63B1 500X160x24 RD x1
3 INLET CONE ED11 500 x1