BCF FIRE 630 T6 1,5kW

BCF FIRE F400
Model
BCF FIRE 630 T6 1,5kW

CENTRIFUGAL DIRECT DRIVE SMOKE FAN WITH BACKWARD CURVED IMPELLER IN SOUNDPROOF CABINET - 400ºC/2H

MANUFACTURING FEATURES
• Box manufactured in galvanised steel sheet.
• Circular inlet flange.
• Backward impeller with self-cleaning system, direct coupling motor.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation type F400 2h.
• Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 3kW, and 400/690V 50Hz for higher powers.
• Exchangeable pannels
• Open drive.

APPLICATIONS
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Maximum working temperature: 60ºC.
• Removing smoke in case of fire. The motor inside the hazardous area (400 ° C / 2 h)


UNDER REQUEST
• Double skin insulation.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2275

Fan

Max flow
12360 m³/h
Weight
218 Kg

Motor

Power
1,5 kW
RPM Motor
940
I max. 400 V
3,71
Size
100L
Weight
28.5 Kg
Efficiency
80 %
FP
0.73

ERP

Fan sheet
Fan type
Unit for non-residential ventilation (LOT 6)
Tipology
Unidirectional
Other
None
Type of driver None
Values Requirements 2018
Max. efficiency (%)
55.38 43.82
Eff. heat recovery (%)
-
Absorbed power (kW) 1.342
Flow (m³/h)
7556.35
Static pressure (Pa)
334.89
Speed (m/s)
6.78
SFP
639.14