MEDIUM PRESSURE FAN WITH BACKWARD CURVED IMPELLER DIRECT DRIVE IN Fe360 SHEET
MANUFACTURING FEATURES:
• Fan made of Fe360 sheet. The fan paint finish is based on a Qualicoat polyester powder coating stoved at 200ºC, with an average film thickness of 70 microns. Average heat resistence of coating is 180ºC with peaks of 200ºC.
• Fully welded housing.
• Single inlet backward impeller with self-cleaning system made of Fe360 sheet statically and dynamically balanced.
Impellers are painted with polyester primer that resists temperatures up to 300ºC.
• Standard asynchronous squirrel-cage motor with IP-55 protection and class F insulation. Manufactured with standard voltages: 230V/400V 50Hz in single phase motors and 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
• Standard orientation LG270.
• It allows adjusting the orientation locally from models 400 to 630. Models sizes from 710 to 1400 size the orientation is fixed.
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Clean and slightly dusty air transport.
• Exhaust after filters, separators and cyclones.
• Pneumatic transport.
• Maximum working temperature: carried air: 130ºC, ambient: 60ºC.
UNDER REQUEST
· Fans for 60Hz and special voltages.
· 2 speed motor.
· C4 or C5 coating painting
· Hot dip galvanized
· Special steel (Cor-Ten A, Hardox...)
· Inox 304 (normal or electropolished finish)
· Inox 316 (normal or electropolished finish)
· Cooling wheel
· Anticaloric paint
· Reinforced housing
· Fully welded housing (waterproof)
· Insulated housing
· Split casing (for big sizes)
· Inspection door to facilitate maintenance and cleaning
· Drain plug.
· Airtight axle
· Frontal foot
· Double suction flange
· Available in the following versions:
- Non-sparking air passage and standard motor.
- ATEX II3GD Ex_na
- ATEX II3G Ex_e
- ATEX II3GD Ex_d
· Other brands of motors.
· Orientation: RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315, LG0, LG45, LG90, LG135, LG180. LG225, LG315.
A | a | a1 | a2 | B | b | b1 | b2 | C | D | d | d1 | D1 | d2 | D2 | D3 | D4 | D5 | D6 | D7 | E | F | G | H | H1 | H2 | I | J | K | L | M | N | N1xØ1 | n1xp | N2xØ2 | n2xp | O | O6 | Ø3 | Ø3 | P | R | S | S1 | S2 | S3 | S4 | S5 | S6 | S7 | T | U | W | X | X1 | X2 | X3 | X4 | X5 | X6 | X7 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
221 | 569 | 629 | 669 | 1446 | 404 | 464 | 504 | 1500 | 630 | 565 | 629 | 1038 | 665 | 905 | 870 | 835 | 721 | 633 | 1179 | 1780 | 703 | 202 | 850 | 630 | 1060 | 701 | 962 | 1026 | 1144 | 800 | 404 | Nº12 M8x25 | 2x160 | 14x14 | 3x160 | 80 | 549 | 20 | 20 | 962 | 39 | 870 | 721 | 633 | 630 | 1179 | 1038 | 905 | 835 | 47 | 1284 | 497 | 721 | 630 | 1179 | 1038 | 905 | 870 | 835 | 633 |
MANUFACTURING FEATURES
• For axial (inlet and outlet) and centrifugal (inlet) fans.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.
MANUFACTURING FRATURES
• Galvanized protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
Nº | Family | Name | Qty |
---|---|---|---|
2 | TURBINE | MBGR 902 T2 160kW LG | x1 |
3 | INLET CONE | MBGR-MTGR 900 | x1 |
4 | MOTOR | 160KW T2 B3 400/690V | x1 |