Product out of catalogue
fan image
Model
MPBID 402 T2 3kW (std)

MPBID 402 T2 3kW (std)

MEDIUM PRESSURE FAN WITH BACKWARD CURVED IMPELLER DIRECT DRIVE IN Fe360 SHEET

 

MANUFACTURING FEATURES:

• Fan made of Fe360 sheet. The fan paint finish is based on a Qualicoat polyester powder coating stoved at 200ºC, with an average film thickness of 70 microns. Average heat resistence of coating is 180ºC with peaks of 200ºC.
• Fully welded housing.
• Single inlet backward impeller with self-cleaning system made of Fe360 sheet statically and dynamically balanced.
Impellers are painted with polyester primer that resists temperatures up to 300ºC.
• Standard asynchronous squirrel-cage motor with IP-55 protection and class F insulation. Manufactured with standard voltages: 230V/400V 50Hz in single phase motors and 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
• Standard orientation LG270.
• It allows adjusting the orientation locally from models 400 to 630. Models sizes from 710 to 1400 size the orientation is fixed.

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Clean and slightly dusty air transport.
• Exhaust after filters, separators and cyclones.
• Pneumatic transport.
• Maximum working temperature: carried air: 130ºC, ambient: 60ºC.

UNDER REQUEST

· Fans for 60Hz and special voltages.
· 2 speed motor.
· C4 or C5 coating painting
· Hot dip galvanized
· Special steel (Cor-Ten A, Hardox...)
· Inox 304 (normal or electropolished finish)
· Inox 316 (normal or electropolished finish)
· Cooling wheel
· Anticaloric paint
· Reinforced housing
· Fully welded housing (waterproof)
· Insulated housing
· Split casing (for big sizes)
· Inspection door to facilitate maintenance and cleaning
· Drain plug.
· Airtight axle
· Frontal foot
· Double suction flange
· Available in the following versions:
    - Non-sparking air passage and standard motor.
    - ATEX II3GD Ex_na
    - ATEX II3G Ex_e
    - ATEX II3GD Ex_d
· Other brands of motors.
· Orientation: RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315, LG0, LG45, LG90, LG135, LG180. LG225, LG315.

Fan

Max flow
3610 m³/h
Weight
81 Kg

Motor

Power
3 kW
RPM Motor
2880
I max. 230 V
10,3
I max. 400 V
5,92
Size
100L
Weight
38.5 Kg
Efficiency
87.1 %
FP
0.86
MPBID 402 T2 3kW (std)
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

MPBID 402 T2 3kW (std)

Dimensions scheme
A a a1 a2 B b b1 b2 C D d d1 D1 d2 D2 D3 D4 D5 D6 D7 E F G H H1 H2 I J K M N1xØ1 n1xp N2xØ2 n2xp O6 Ø3 Ø3 Q R S S1 S2 S3 S4 S5 S6 S7 X X1 X2 X3 X4 X5 X6 X7
105 258 292 328 560 185 219 255 655 285 255 292 483 325 387 400 353 315 306 543 815 319 95 500 285 500 197 289 324 276 Nº8 M8x20 1x112 10x12 2x112 258 12 12 30 49 400 315 306 285 543 483 387 353 315 285 543 483 387 400 353 306

MPBID 402 T2 3kW (std)

Electrical scheme

MPBID 402 T2 3kW

Model
INT 25 3P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
BA-400 25
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
RA 255x8
Information
INLET PROTECTION GUARD FOR CENTRIFUGAL FANS

MANUFACTURING FRATURES

• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.

Model
RI 258x185
Information
OUTLET PROTECTION GUARD FOR FANS

MANUFACTURING FRATURES

• Galvanized protection grid on the outlet side to avoid the entry of objects and contact with the impeller.

Model
EI 258x185-250
Information
CIRCULAR OUTLET CONNECTION FLANGE

MANUFACTURING FEATURES

• Connection to be fitted in the centrifugal fans outlet.
• Manufactured in galvanized steel.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
AC 250
Information
CONNECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
SFC 400 III 8A *
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

MPBID 402 T2 3kW (std)

Spare parts scheme
Family Name Qty
2 TURBINE MBGR 402 T2 3kW LG x1
3 INLET CONE MBGR-MTGR 400 x1
4 MOTOR 3KW T2 B3 230/400V x1