fan image
Model
CJF FIRE 100N F400

CJF FIRE 100N F400

LOW PROFILE CENTRIFUGAL JET FAN - 400ºC/2h

MANUFACTURING FEATURES

FAN
• Galvanized steel sheet casing.
• Strong backward impeller with self-cleaning system made of strong galvanized steel sheet.
• External wiring box.
• Inlet protection.
• Feet included.

MOTOR
• Class H insulation, S1 continuous use and S2 emergency use, with bearing balls, IP-55 protection, 2 speeds.
• 400V 4/8 poles Dalhander three phase motor.
• Maximum working temperature:
• S1 -> -20ºC +60ºC.
• S2 -> 400ºC / 2h.

APPLICATIONS

• Conceived for car parkings and large spaces where polluted air, or smoke from a fire, needs to be removed effectively. An optimized design minimizes the height needed for their installation.
• Maximum working temperature: 60ºC.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-3089

Fan

Max flow
9200 m³/h
Weight
130 Kg

Motor

Power
2,2/0,37 kW
RPM Motor
1430/705
I max. 400 V
5,6/1,8
CJF FIRE 100N F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

CJF FIRE 100N F400

Dimensions scheme
A B C D E F H I K L Thrust (N)
1600 300 1000 351,5 1093 1052 800 250 13 4 97/25

CJF FIRE 100N F400

Electrical scheme

CJF FIRE 100N F400

Model
INT 400 25A 6P
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
INT 25 6P A
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)