fan image
Model
WMA FIRE 125 T6 (A6:6) F300

WMA FIRE 125 T6 (A6:6) F300

WALL-MOUNTED AXIAL SMOKE FAN WITH CAST ALUMINUM IMPELLER DIRECT DRIVE - 300ºC/1h

MANUFACTURING FEATURES

• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminum impeller with variable pitch angle.
• Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 300ºC/1h. Standard voltages 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.


APPLICATIONS

Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Maximum working temperature: 60ºC.

UNDER REQUEST

• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2406

Fan

Max flow
89910 m³/h
WMA FIRE 125 T6 (A6:6) F300
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

WMA FIRE 125 T6 (A6:6) F300

Dimensions scheme
C (Mot.T.132) C (Mot.T.160L) C (Mot.T.160M) C (Mot.T.180L) C (Mot.T.180L) C (Mot.T.180M) C (Mot.T.200) C (Mot.T.200) C (Mot.T.225) C (Mot.T.225) E O ØA ØB ØD ØJ
759 759 759 779 779 760 863 863 948 948 340 20x18º 1365 1320 1263 15

WMA FIRE 125 T6 (A6:6) F300

Electrical scheme

WMA FIRE 125 T6 (A6:6) F300

Model
RP0 1250
Information
Outlet protection guard for axial fans

MANUFACTURING FRATURES

• Protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.

UNDER REQUEST

• Stainless guard 304 or 316 with electro-polished finishing coat.

Model
AC 1250
Information
CONNECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
BAD 21
Information
CIRCULAR-CIRCULAR ANTI-VIBRATION FLANGE

MANUFACTURING FEATURES

• Circular-circular coupling flange through anti-vibration canvas.
• Fire resistance M0: from -50ºC to +200ºC in continuous and 400ºC/2h