Product out of catalogue
fan image
Model
HPTVM 2000

HPTVM 2000

HIGH PRESSURE FAN WITH HIGH EFFICIENCY BACKWARD CURVED IMPELLER BELT DRIVE IN Fe360 SHEET

 

MANUFACTURING FEATURES:

• Fan made of Fe360 sheet. The fan paint finish is based on a Qualicoat polyester powder coating stoved at 200ºC, with an average film thickness of 70 microns. Average heat resistence of coating is 180ºC with peaks of 200ºC.
• Fully welded housing.
• High efficiency simple inlet backward impeller with self-cleaning system made of Fe360 sheet statically and dynamically balanced. Impellers are painted with polyester primer that resists temperatures up to 300ºC.
• Motorized fan with basement (configuration 12). Full equipped fans including: motor, pulleys, belts, belts guard and shaft guard. Fitted over a base plate.
• Standard orientation LG270.
• It allows adjusting the orientation locally from models 350 to 630. Models sizes from 710 to 2000 size the orientation is fixed.

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Clean and slightly dusty air transport.
• Exhaust after filters, separators and cyclones.
• Pneumatic transport.
• Maximum working temperature: carried air: 200ºC, ambient: 60ºC.

UNDER REQUEST

· Fans for 60Hz and special voltages.
· 2 speed motor.
· Fan with free shaft (configuration 1) or with motor supported on the pedestal side (configuration 9).
· C4 or C5 coating painting
· Hot dip galvanized
· Special steel (Cor-Ten A, Hardox...)
· Inox 304 (normal or electropolished finish)
· Inox 316 (normal or electropolished finish)
· Cooling wheel
· Anticaloric paint
· Reinforced housing
· Fully welded housing (waterproof)
· Insulated housing
· Split casing (for big sizes)
· Inspection door to facilitate maintenance and cleaning
· Drain plug.
· Airtight axle
· Frontal foot
· Double suction flange
· Available in the following versions:
    - Non-sparking air passage and standard motor.
    - ATEX II3GD Ex_na
    - ATEX II3G Ex_e
    - ATEX II3GD Ex_d
· Other brands of motors.
· Orientation: RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315, LG0, LG45, LG90, LG135, LG180. LG225, LG315.

Fan

Max flow
104440 m³/h
HPTVM 2000
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

HPTVM 2000

Dimensions scheme
A a a1 a2 B b b1 b2 C D d d1 D1 d2 D2 D3 D4 D5 D6 D7 E F G H H1 H2 I J K L M N N1xØ1 n1xp N2xØ2 n2xp N3 N4 O O6 Ø3 Ø4 P Q R R' S S1 S2 S3 S4 S5 S6 S7 T T1 U U' V V1 X X1 X2 X3 X4 X5 X6 X7 Y
434 801 871 921 2065 569 639 689 2840 1320 1007 1067 1664 1107 1556 1520 1475 1343 1246 2109 3143 1203 462 1500 1320 1500 2030 917 754 1100 60 85 Nº24 M10x30 2x200 16x12 3x200 170 65 917 789 30 30 754 210 65 85 1520 1343 1246 1320 2109 1664 1556 1475 60 28 2030 2030 1350 100 1343 1320 2109 1664 2556 1520 1475 1246 250

HPTVM 2000

Electrical scheme

HPTVM 2000

Model
AC 1000
Information
CONNECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
BA-400 100
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
RA 1007x24
Information
INLET PROTECTION GUARD FOR CENTRIFUGAL FANS

MANUFACTURING FRATURES

• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.