MEDIUM PRESSURE FAN WITH BACKWARD CURVED IMPELLER DIRECT DRIVE IN Fe360 SHEET
MANUFACTURING FEATURES:
• Fan made of Fe360 sheet. The fan paint finish is based on a Qualicoat polyester powder coating stoved at 200ºC, with an average film thickness of 70 microns. Average heat resistence of coating is 180ºC with peaks of 200ºC.
• Fully welded or joined housing.
• Single inlet backward impeller with self-cleaning system made of Fe360 sheet statically and dynamically balanced. Impellers are painted with polyester primer that resists temperatures up to 300ºC.
• Standard asynchronous squirrel-cage motor with IP-55 protection and rated class F insulation. Manufactured with standard voltages: 230/400V 50Hz for three phase motors up to 4kW and 400/690V 50Hz for higher powers.
• Standard orientation LG270.
• It allows adjusting the orientation locally from models 250 to 630. Models sizes from 710 to 1400 size the orientation is fixed.
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Dusty air and small loads of pellet materials transport.
• Exhaust after filters, separators and cyclones.
• Pneumatic transport.
• Maximum working temperature: carried air: 130ºC, ambient 60ºC.
UNDER REQUEST
· Fans for 60Hz and special voltages.
· 2 speed motor.
· C4 or C5 coating painting
· Hot dip galvanized
· Special steel (Cor-Ten A, Hardox...)
· Inox 304 (normal or electropolished finish)
· Inox 316 (normal or electropolished finish)
· Cooling wheel
· Anticaloric paint
· Reinforced housing
· Fully welded housing (waterproof)
· Insulated housing
· Split casing (for big sizes)
· Inspection door to facilitate maintenance and cleaning
· Drain plug.
· Airtight axle
· Frontal foot
· Double suction flange
· Available in the following versions:
- Non-sparking air passage and standard motor.
- ATEX II3GD Ex_na
- ATEX II3G Ex_e
- ATEX II3GD Ex_d
· Other brands of motors.
· Orientation: RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315, LG0, LG45, LG90, LG135, LG180. LG225, LG315.
A | a | a1 | a2 | B | b | b1 | b2 | C | D | d | d1 | D1 | d2 | D2 | D3 | D4 | D5 | D6 | D7 | E | F | G | H | H1 | H2 | I | J | K | L | M | N | N1xØ1 | n1xp | N2xØ2 | n2xp | O | O6 | Ø3 | Ø3 | P | R | S | S1 | S2 | S3 | S4 | S5 | S6 | S7 | T | U | W | X | X1 | X2 | X3 | X4 | X5 | X6 | X7 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
246 | 638 | 698 | 738 | 1565 | 453 | 513 | 553 | 1342 | 560 | 635 | 698 | 929 | 735 | 811 | 782 | 749 | 641 | 562 | 1053 | 1591 | 560 | 226 | 755 | 560 | 950 | 675 | 862 | 926 | 1044 | 800 | 453 | Nº12 M10x30 | 2x160 | 14x14 | 3x160 | 80 | 493 | 20 | 20 | 862 | 65 | 782 | 641 | 562 | 560 | 1053 | 929 | 811 | 749 | 47 | 1333 | 546 | 641 | 560 | 1053 | 929 | 811 | 782 | 749 | 562 |
MANUFACTURING FEATURES
• For axial (inlet and outlet) and centrifugal (inlet) fans.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.
MANUFACTURING FRATURES
• Galvanized protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
Nº | Family | Name | Qty |
---|---|---|---|
2 | TURBINE | MBRU 802 T2 110kW LG | x1 |
3 | INLET CONE | MBRU-MTRU 800 | x1 |
4 | MOTOR | 110KW T2 B3 400/690V | x1 |